The MEAT auto power transfer system, based on flexible combination of air circuit breaker and E2/E3 controllers, allows reliable switching of multi-power supplies, and realize the function of two incoming lines with one bus-tie. The MEAT controller can help to monitor undervoltage, overvoltage and phase loss of two power supplies. In case of exceptions from any phase of the power supply circuit, the controller can automatically send the switching command to the air circuit breaker according to the preset program.
The automatic power conversion system controller and air circuit breaker are all CCC certified
The automatic power conversion system has automatic operation, remote operation, communication operation, manual operation mode, and can preferentially cut off all power supplies through the fire linkage function in emergency
The switchover delay of the automatic power conversion system ranges from 0 to 480s. If the delay time is set to 0, the switchover operation time is less than 1s
It has the function of automatic charge and automatic recovery, automatic charge without recovery
It features the conversion between the two mains, the conversion between the mains and the generator, the conversion between the two inlet lines and the busbar